Have a question? Give us a call: +86-577-6270-6808

Aluminium Alloy Strain Clamp And Insulation Cove (NXL)

Short Description:

Model NO.:NXL

Nll-1 Insulation Cove: Nll-2 Iinsulation Cover

OEM: Accept

Trademark: Pengyou

Transport Package: as Your Requested

Specification: NXL/NLL

Origin: Zhejiang, China

1. Material: High-intersity oxidate-resistanle aluminium alloy

2. Excellent weather proof performance

3. Accurate delivery


Product Detail

Product Tags

Application:

NXL Series strain clamp is suitable for distribution wire up to 10KV, firstly ,fix the aerial insulation aluminum conductor or naked aluminum conductor on the rotate angle or insulator of terminal strain pole, and then fix and tight the aerial conductor

Structure feature:

 Choose the unmagnetic character high-intersity oxidate-resistanle aluminium alloy,No waste electric energy
 Wedged-Locked structure,easy-installation
 An arc embraces the most part,conductor cannot change. Large grip strength.
Insulation cover performance feature
 Withstand voltage:  18kV keep voltage one minute not breakdown
 Insulation resistance:>1.0×1014 Ω
 Environments temperature:-30ºC ~ 90ºC
Specification
Catalog No. section(mm²) Length L1(mm) Grip strength(kN) Failure load(kN) Insulation cover type
NXL-1 50 245 5.16 14.5 NXL-95
70 7.12
95 9.4
NXL-2 120 255 12.7 23.4 NXL-150
150 15.2
NXL-3 185 300 18.5 36.3 NXL-240
240 23.6
NXL-4 Ø22.5~27.5mm 320 55 61 NXL-4
Catalog No. section(mm²) Length L1(mm) Length L1(mm) Grip strength(kN) Failure load(kN) Insulation cover type
NXL-2J 10kV 35 Does not strip the insulation 3.4 14.5 Suitable for 10KV insulated aluminum wire
50 4.6
70 6.7
NXL-3J 10kV 95 8.9 23.4
120 11.3
150 13.6
NXL-4J 10kV 185 17.3 36.3
240 22.5
Catalog No. Section
Conductor(mm)
Dia(mm) Grip strength(kN) Failure load(kN)
NXLJ-1 LGJ-35/6 8.16 11.4 38
LGJ-50/8 9.6 15.2
LGJ-70/10 11.4 21
LJ-35~70 7.5~10.8 5.2~9.9
1kV/35~50 No peeling 3.36~4.5
NXLJ-2 LGJ-95/15 13.61 31.5 50
LGJ-120/7 14.5 24.8
LGJ-150/8 16 29.6
LJ-95~150 12.48~15.75 13~21
1kV/70~120 No peeling 6.7~11.2
10kV35~70 No peeling 3.3~6.7
LGJ185/10 18 36.8
NXLJ-3 LGJ-240/30 21.6 68 70
LJ-185~240 17.50~20 25.6~32.6
1kV/150~240 No peeling 13.6~23
10kV/95~150 No peeling 8.9~13.6
Part No. Applicable
Conductor (mm)
Rated  Failure
Load  (KN)
C M  U bolts
NLL-1 5.0-10.0 18 16 M12*2 40
NLL-2 10.0-14.0 18 16 M12*2 40
NLL-3 14.0-18.0 28 18 M14*3 70
NLL-4 18.0-23.0 34 18 M16*3 90
NLL-27 12.48-21.66 30 18 M16*4 90
NLL-5 23.0-29.0 36 18 M16*5 100
NLL-6 25.9-32.67 40 22 M16*5 100

  • Previous:
  • Next:

  • Write your message here and send it to us